ELECTRICAL FUNDAMENTALS

What is Power Factor in Electric Motors?

Power factor measures how effectively a motor converts the current it draws into useful work. This guide explains real, reactive and apparent power, why motors have a power factor below one, and why it matters for cost and infrastructure.

Published 10 July 2026 · Updated 11 July 2026

Real, reactive and apparent power

In an alternating-current circuit, not all the power drawn from the supply is converted into useful work. Real power, measured in kilowatts (kW), is the portion that actually performs work, such as turning a shaft or producing heat. Reactive power, measured in kilovolt-amperes reactive (kVAR), flows back and forth between the source and the magnetic and electric fields of the load without doing net work, yet it is essential for establishing those fields.

The combination of the two, as seen by the supply, is the apparent power, measured in kilovolt-amperes (kVA). The three quantities are related by the so-called power triangle: apparent power is the vector sum of real and reactive power. Power factor is simply the ratio of real power to apparent power, a dimensionless number between zero and one.

A power factor close to one means almost all the supplied power is doing useful work. A lower value means a larger share is circulating as reactive power, so the supply must deliver more current to achieve the same useful output. The table below sets out the three powers side by side.

QuantityUnitWhat it does
Real powerkWPerforms useful work, such as producing shaft torque or heat; the power that is actually converted to output
Reactive powerkVARSustains the magnetic and electric fields the load needs but does no net work; oscillates between source and load
Apparent powerkVAThe total power the supply must provide, combining real and reactive power; determines the current the system must carry

Why motors have a power factor below one

Electric motors are inductive loads: they need reactive power to magnetise their iron cores and establish the rotating magnetic field that produces torque. This magnetising requirement means an induction motor always draws some reactive power, so its power factor is inherently less than one even when it is perfectly healthy and correctly applied.

The magnetising component is relatively fixed, while the real-power component rises and falls with mechanical load. As a result, power factor is strongly load-dependent. At rated load an induction motor commonly exhibits a power factor in the region of 0.7 to 0.9, but at light load the fixed magnetising current dominates and the power factor falls markedly.

This behaviour explains why an oversized motor running well below its rated load is doubly penalised: it is both less efficient and operating at a poorer power factor than it would near its design point. Right-sizing a motor to its duty is therefore one of the simplest ways to keep power factor healthy.

Why power factor matters

Poor power factor increases the current a system must carry for a given amount of useful work. Higher current means greater resistive losses in cables, transformers and switchgear, and it consumes capacity that could otherwise serve additional load. In effect, a low power factor makes the whole electrical distribution system work harder for the same output.

For larger consumers, network operators frequently levy charges based on apparent power or impose penalties for poor power factor, because the utility must size its infrastructure for the current actually drawn rather than the useful power delivered. Improving power factor can therefore reduce demand charges as well as internal losses.

Power factor should not be confused with efficiency, though the two are related in effect. Efficiency describes how much of the real input power becomes useful output; power factor describes how much of the apparent power is real. A motor can be efficient yet still burden the supply with reactive current, which is why both metrics deserve attention.

Power factor and motor technology

Different motor technologies present different power-factor characteristics. Conventional induction motors always draw magnetising current from the supply, which sets a ceiling on their achievable power factor. Line-fed synchronous machines can be arranged to run at, or even above, unity power factor, and some can supply reactive power to the network.

When a motor is fed through a variable speed drive, the picture changes again. The drive decouples the motor from the mains, and the input stage of the drive largely determines the power factor seen by the supply. Modern drives with appropriate front-end designs can present a high power factor to the network regardless of the motor's own magnetising behaviour, though they introduce other considerations such as harmonic content.

Because technology choice affects power factor, it is worth considering alongside efficiency class and materials when specifying a drive system. The best combination depends on the application, the duty cycle and how the installation connects to the wider network.

Improving power factor

The classic remedy for poor power factor is power-factor correction, most commonly by connecting capacitors that supply reactive power locally so that it need not be drawn all the way from the source. Correction can be applied at an individual motor, at a distribution board, or centrally for a whole installation, each with its own trade-offs in cost and flexibility.

Other measures work by reducing the reactive demand in the first place. Right-sizing motors to their load keeps them near their design point where power factor is best, while switching off or unloading idle machines avoids the light-load penalty. Where variable speed operation is needed, a drive with a high-power-factor front end can address the issue at source.

Any correction scheme should be designed with care, because over-correction, resonance with system harmonics or switching transients can cause problems of their own. Measurement and, where appropriate, expert design ensure that correction delivers the intended benefit without unintended side effects.

Frequently asked questions

What is a good power factor for a motor?

A power factor close to one is ideal, meaning almost all the supplied power does useful work. At rated load, induction motors typically sit somewhere around 0.7 to 0.9. Values fall at light load because the magnetising current becomes proportionally larger.

Is power factor the same as efficiency?

No. Efficiency is the ratio of useful output power to real input power, whereas power factor is the ratio of real power to apparent power. A motor can be efficient yet still draw significant reactive current. Both metrics matter but describe different things.

Why do induction motors have a power factor below one?

Induction motors are inductive loads that need reactive power to magnetise their cores and create the rotating field. This magnetising requirement means they always draw some reactive current, so their power factor is inherently less than one. The value worsens as mechanical load falls.

How can I improve power factor?

The most common method is power-factor correction using capacitors that supply reactive power locally. Right-sizing motors, avoiding light-load running and using drives with high-power-factor front ends also help. Correction schemes should be designed carefully to avoid resonance or over-correction.

Does a variable speed drive change power factor?

Yes. A drive decouples the motor from the mains, so the drive's input stage largely determines the power factor seen by the supply. Modern drives with suitable front ends can present a high power factor regardless of the motor's own magnetising behaviour, though they may introduce harmonics that need managing.

EKMO Motor Licensing

IE6 ferrite motors. Production-ready. Available for licensing now.

30+ years of ferrite motor engineering. No neodymium. No dysprosium. No export-license exposure. Power range 20–800 kW, frames 225–355+. A licensee can reach production in under 12 months.

See EKMO IE6 ferrite motors →

Related pages

Ferrite MotorMotor EngineeringRare-Earth-Free MotorsGuide: Efficiency at Partial LoadGuide: What is IE6 EfficiencySee EKMO IE6 ferrite motors